**The short answer:** under the 25% rule, a grease interceptor must be pumped out before the floating grease plus the settled solids reach 25% of the liquid depth (or capacity) of the unit. You find the percentage by measuring, not by counting days: `(FOG depth + solids depth) ÷ total liquid depth × 100`. If the result is 25 or more, the interceptor was pumped too late and the pumping interval has to get shorter. Most cities then add a calendar backstop on top, so the real rule is "25% or every N days, whichever comes first."
That is the version everyone repeats. The version that decides whether a restaurant gets a notice of violation is messier, because cities do not agree on the denominator, the chamber, the sampling method, or the backstop. This post goes through what the actual documents say.
Running this manually today?
See how Fieldproxy handles it: a walkthrough on your own workflow, not a canned demo.
Get DemoThe formula, as cities publish it
Halifax Water's maintenance diagram shows it as `% Full = (A + B) ÷ C × 100`, where A is the FOG layer, B is the settled solids and C is the total depth of the contents. Its example: 20 cm of FOG and 15 cm of solids in 95 cm of liquid is 36.8% after one month, so the interceptor should have been serviced sooner. Two weeks after a cleaning, 10 cm and 10 cm in 95 cm is 21.05%, so the interceptor was fine and a two-week schedule suits that restaurant (Halifax Water, Grease Interceptor Maintenance diagram).
New Orleans' Sewerage and Water Board uses feet. Its handout asks whether 0.5 ft of FOG plus 1.0 ft of solids in 4.0 ft of interceptor contents meets the rule: 1.5 ÷ 4.0 is 37.5%, so the 25% rule is exceeded and pump-out frequency must go up (Sewerage and Water Board of New Orleans, Grease Traps 101).
The arithmetic is the same everywhere. What changes is below.
What changes from city to city
What changes from city to city
| Jurisdiction | Threshold and measurement | Calendar backstop |
|---|---|---|
| Tacoma, WA | Clean when 25% of the chamber is filled with FOG and solids (<a href="https://www.cityoftacoma.org/UserFiles/Servers/Server_6/File/ES/Compliance/FOG%20Sizing%20and%20Installation%20Policy%20Clarification%20Sheet%201.2025.pdf">Tacoma FOG sizing policy, Jan 2025</a>) | None stated on that sheet |
| Halifax, NS | 25% or more of the total volume of the interceptor | Once per month, whichever comes first |
| New Orleans, LA | 25% of the interceptor's overall liquid depth (handout) or 25% of design capacity (plumbing code section quoted in the same document) | At least quarterly |
| Pleasanton, CA | Floatable and bottom solids above 25% of the usable volume (water level); a new frequency must be set | Gravity interceptors every 60 days unless the City says otherwise; traps cleaned at least every 2 weeks |
| Lancaster, PA | 25% of overall liquid depth by dipstick or sludge judge; pump out within 5 days of discovery | Completely evacuated every 90 days, and fully evacuated, cleaned and inspected at least every 180 days |
| Apex, NC | Out of compliance at 35% of total depth in the inlet chamber or 25% in the outlet chamber, or more than 4 inches of grease cap anywhere in the interceptor | Not in the SOP |
| Calgary, AB | 25% of the interceptor capacity, or a FOG layer thicker than 2 inches | At least once every four weeks |
| Austin, TX | Not 25%: 50% of wetted height, measured from the bottom to the invert of the outlet | At least every 90 days |
Sources for the rows above: the Halifax and New Orleans documents linked earlier, plus Pleasanton's Sewer Pipe Blockage Control Program manual, Lancaster's FOG Control Program Manual (Jan 2019), Apex's SOP 002: FOG Inspection Plan, Calgary's grease interceptor guide and Austin's grease trap maintenance page.
Three things in that table trip people up.
**1. The denominator is not always the same.** Tacoma says the chamber, New Orleans says liquid depth in one document and design capacity in another, Pleasanton says usable volume measured at the water level, and Austin measures to the outlet invert. For a tank with straight sides, depth and volume percentages are nearly the same. For a unit with a sloped bottom, a baffle wall or an oversized dead zone above the outlet, they are not. The only safe move is to use the denominator the inspector for that sewer authority uses.
**2. Apex splits the chambers.** A two-compartment interceptor can pass in the outlet chamber and fail at the inlet. The Apex SOP tells the inspector to lower the sludge judge slowly, shake it gently once it passes through the grease mat, and compare against 35% at the inlet and 25% at the outlet. Hydromechanical units get a different test: a screwdriver moved through the wastewater, failing if there is no visible separation of grease and water. A hauler who only reads the first compartment is not checking the thing the inspector checks.
**3. "Pump within 5 days" is its own deadline.** Lancaster's manual says that once an inspector finds more than 25% of the liquid depth full of FOG and solids, the interceptor must be pumped out within 5 days of discovery. The clock starts at the inspection, not at your next scheduled visit.
The calendar side: a formula for days between pumps
The 25% rule tells you when you were late. It does not tell you the interval to schedule. Independence, Missouri publishes a worksheet that does, and it is one of the few places the math is written out (City of Independence, Grease Interceptor Clean-Out Frequency Worksheet, revised 27 July 2022).
- Interceptor capacity in pounds = gallons × 0.25 × 0.7 × 7.5. That bakes in the 25% rule, a 70% grease-to-solids ratio and 7.5 lb of FOG per gallon. The worksheet's own table lists 1,000 gal as 1,300 lb, 1,500 gal as 1,970 lb and 750 gal as 980 lb.
- Grease production per meal depends on the menu. Without flatware: low 0.005 lb (sandwich shop, bar, ice cream parlor), medium 0.025 lb (cafe, pizza, Thai or Japanese), high 0.035 lb (family restaurant, fast food, buffet, Italian), very high 0.058 lb (steak house, seafood, Mexican, Chinese, fried chicken, barbecue). With flatware the figures rise to 0.0065, 0.0325, 0.0455 and 0.075.
- Days per cycle `D = V ÷ (M × G)`, where V is capacity in pounds, M is meals or customers per day and G is grease per meal. The worksheet allows a minimum of 30 days and a maximum of 90.
Worked example
A barbecue restaurant serves 600 meals a day without flatware (very high, 0.058 lb per meal), so it produces 600 × 0.058 = 34.8 lb of grease a day.
| Interceptor | Capacity | Days to fill to 25% | Schedule |
|---|---|---|---|
| 750 gal | 980 lb | 28.2 days | 30 days (the worksheet's floor, so it is undersized for this menu) |
| 1,000 gal | 1,300 lb | 37.4 days | Every 37 days |
| 1,500 gal | 1,970 lb | 56.6 days | Every 56 days |
The same 1,500 gal interceptor at a sandwich shop doing 200 meals a day (0.005 lb) fills at 1 lb a day, which gives 1,970 days on paper, so the 90-day maximum applies instead. The formula is a starting estimate. The sludge judge reading at the next visit confirms or overrides it.
How to take the reading so it survives an inspection
- **Sample the way the sewer authority does.** Check the document for the inlet chamber, the outlet chamber or both (Apex and Pleasanton differ here).
- **Break through the grease mat before reading.** A sludge judge is a clear tube with a ball valve at the bottom. Apex's inspectors shake it gently once it passes the grease mat and keep shaking if the wastewater is thick.
- **Record three numbers, not one:** FOG depth, solids depth and total liquid depth, in the same units. Then record the computed percentage. A note that says "heavy" is not a reading.
- **Decide before you pump.** Taking the reading before the vacuum truck hooks up is the only way to know whether the last interval was too long.
- **Write down the recommendation.** Pleasanton says the City advises the restaurant of the frequency at which 25% is being met or exceeded, and may recommend a specific pumping frequency. Haulers who log the same advice and the restaurant's answer protect themselves when the next inspection finds 40%.
- **Keep the records the utility asks for.** Pleasanton wants date, hauler, gallons of FOG removed and the manifest kept on site for at least 2 years. Calgary also says two years. Austin says manifests are kept three years.
What the rule does not tell you
The EPA's National Pretreatment Program fact sheet puts it plainly: required maintenance frequency depends greatly on how much FOG a facility generates and on the best management practices it uses, and a kitchen that adopts them can often cut its pumping frequency (US EPA, Controlling Fats, Oils, and Grease Discharges from Food Service Establishments). The 25% number is a cleanliness threshold, not a schedule. Menu changes, a new fryer, a switch to or from flatware, a catering contract or a seasonal rush all move the interval, which is why a once-a-year "we pump every 60 days" assumption drifts.
How to set this up
For a pumper, the spreadsheet version of this works until about the third utility. After that, the thresholds, deadlines and denominators live in different heads.
The grease trap pumping software guide lays out the full build. For this specific rule, the pieces are:
- **A record per device** carrying the utility's threshold (25% of depth, 25% of usable volume, 35% inlet and 25% outlet, 50% of wetted height), its calendar backstop, its 5-day or similar corrective deadline, and the formula inputs: capacity, menu class, meals per day.
- **A reading form** on the driver's phone with required fields for FOG, solids and liquid depth, a computed percentage against that device's rule, and photos of the open interceptor.
- **<a href="/agents/watcher-agent">Watcher agent</a>:** flags any device whose reading came back at or above its threshold, and any device whose calendar backstop passes without a completed pump.
- **<a href="/agents/vision-agent">Vision agent</a>:** reads the photo of the sludge judge and proposes the three depths so the driver confirms instead of types.
- **<a href="/agents/autopilot">Autopilot</a>:** drafts the note to the restaurant manager recommending a shorter interval after a failed reading, and chases the answer. A person approves before it sends.
- **<a href="/agents/scheduler-agent">Scheduler agent</a>:** a weekly list of devices due in the next 14 days by utility, with the filing deadline for each.
FAQ
**Is the 25% rule a law?** Not by itself. It is a threshold written into individual city, utility or district rules, and sometimes only into guidance. Pleasanton's manual says it adopted the rule as a standard from its wastewater treatment provider, the Dublin San Ramon Services District. Always read the local ordinance or the restaurant's discharge permit.
**Does the 25% apply to traps under the sink?** Usually not in the same form. Small hydromechanical traps are generally on a fixed short cycle. Pleasanton's manual calls for weekly inspection and cleaning at least every 2 weeks, and Apex tests hydromechanical units by whether grease and water visibly separate rather than by a depth percentage.
**What if the interceptor passes at 24% on the day but fails a week later?** The rule is a snapshot. That is why cities add calendar caps (30 days in Halifax, 90 days in Lancaster, quarterly in New Orleans) and why a reading of 24% is a signal to shorten the interval, not a reason to extend it.
**Can I extend the interval if every reading is low?** Where the utility allows it, yes, up to the calendar maximum. The Independence worksheet caps the cycle between 30 and 90 days. Keep the readings, because they are the evidence for the longer interval.
**Who is liable if the line backs up?** The sewer authority's documents are clear that the establishment owner pays. New Orleans says the Sewerage and Water Board holds business owners liable for all costs of removing FOG from the sewer system, including damage to adjoining property, streets and sewer repair. Lancaster says costs for maintenance, repair and pumping fall on the establishment owner.
**Why does Austin use 50%?** Austin's code (section 15-10-197) is written around grease traps pumped at least every 90 days, or sooner when grease and solids make up 50% or more of the wetted height measured from the trap bottom to the outlet invert. It is a different rule, not a typo of the 25% rule.