Radon Retest Schedule After Mitigation: 24 Hours, 30 Days, 2 Years and 5 Years, Explained

Fieldproxy Team - Field Operations Research
12 min read

Written by the Fieldproxy team with AI assistance. Results we attribute to a company come only from our published customer stories.

radon mitigationpost-mitigation testradon retestANSI/AARSTASD systemradon compliance

**The short answer:** the first test after a radon mitigation system goes in is a short-term test that starts no sooner than 24 hours after the fan is running and is placed within 30 days of installation (ANSI/AARST SGM-SF, section 9.2). After that, the standard tells the owner to retest at least every 2 years, and also whenever the building, the system or a sale changes. The 24 hours, 30 days and 2 years are the three numbers people remember. The rules around them, closed-building conditions, test length, test location, who may run the test and what the contractor owes if nobody answers, are where jobs go wrong.

This post walks through what the documents say, with one worked timeline, and then what a mitigation company has to track so that none of the clocks lapses.

Running this manually today?

See how Fieldproxy handles it: a walkthrough on your own workflow, not a canned demo.

Get Demo

The three clocks in one table

The three clocks in one table

ClockNumberWhere it comes from
Earliest the first test can start24 hours after the system is operational<a href="https://standards.aarst.org/SGM-SF-2017/39/">ANSI/AARST SGM-SF 2017, section 9.2</a>; the <a href="https://standards.aarst.org/MAH-2019/13/">MAH 2019 protocol, section 7.3.2</a> measures it from fan activation or completion of other mitigation work
Latest the first test should be placed30 days after installation, with an exception for later retests in section 13.6.2<a href="https://standards.aarst.org/SGM-SF-2017/39/">SGM-SF section 9.2</a>
Closed-building conditions before and during the test12 hours before and throughout<a href="https://standards.aarst.org/MAH-2019/13/">MAH 2019, section 7.3.2</a>
Continuous monitor data neededAn average that represents no less than 46 hours of contiguous data collected after both conditions (24 hours, closed building) are met<a href="https://standards.aarst.org/MAH-2019/13/">MAH 2019, section 7.3.2</a>
Pennsylvania short-term test length48 hours to 90 days<a href="https://www.law.cornell.edu/regulations/pennsylvania/25-Pa-Code-SS-240-310">25 Pa. Code 240.310</a>
Ongoing retest adviceAt least every 2 years to verify the system still works; every 5 years for the building generally<a href="https://standards.aarst.org/MAH-2019/19/">MAH 2019, section 8.5.9</a>
EPA's level to fix a home4 pCi/L or higher; consider fixing between 2 and 4<a href="https://www.epa.gov/radon/epa-map-radon-zones">US EPA, Map of Radon Zones</a>

Note that SGM-SF is the standard for existing single-family homes. Multifamily and commercial buildings fall under different AARST documents, and states may add their own rules, so check which one governs the job.

Why 24 hours, and why the fan has to be on

The fan has to run long enough for the soil gas pressure under the slab to settle into its new pattern. The standard's wording is plain: a short-term measurement "no sooner than 24 hours after a mitigation system is operational." The MAH protocol adds that closed-building conditions (windows closed, external doors closed except for normal entry and exit) start at least 12 hours before and continue through the test. If either condition is not met, the test is either postponed until both are, or, with a continuous monitor, extended so the reported average covers at least 46 hours of data that were collected after both conditions held.

Pennsylvania adds its own device rules for any test that has to be reported to the state: at least 3 feet from exterior doors, windows or ventilation ducts, at least 20 inches but not more than 6 feet off the floor, at least 7 feet from sump pits, and never in bathrooms, kitchens, closets, crawl spaces or within 10 feet of a washer or dryer (25 Pa. Code 240.310).

Where the test goes

MAH section 7.3.3 says to test in the same location(s) as the pre-mitigation test, or in the lowest level that could be occupied, and also in the lowest livable area above a crawl space that is structurally isolated from the tested rooms. If the ASD system exhausts below the roof, the advisory is to add a test in the room next to the outside exhaust location. Pennsylvania requires short-term tests in the lowest livable level of each structural zone that contacts the soil.

This is why a contractor who "just dropped a kit in the basement" can fail a state protocol audit even with a low number.

Who is allowed to run the test

SGM-SF section 9.2.3 lists three people who can satisfy the contractor's obligation: an independent qualified measurement professional, the installing contractor if they are also qualified and local law allows it, or the owner or occupant. To avoid the appearance of a conflict of interest, the contractor "shall recommend" an independent professional. The test device has to be on the NRPP or NRSB approved list, or whatever the state requires (section 9.2.4).

The standard also covers the case where the client goes silent. If the client or their representative refuses access, is nonresponsive, or is barred by law from being contacted, the contractor's obligation to obtain test data is treated as satisfied, but if access is refused or reasonable efforts across 3 months after installation get no response, the contractor must forward a test kit to the property in care of the current occupant. The lab must be NRPP, NRSB or state listed, and should be told to send a copy of the result to the contractor.

A worked timeline

Take a sale with a closing date and an escrow holdback. The numbers below combine the SGM-SF and MAH rules with a standard 48-hour test. A state may require more.

Day and timeEventWhy it matters
Mon 9:00Fan switched on, startup manometer reading written on the label next to the gaugeSGM-SF 9.1.1 requires the suction in the riser to be measured and recorded at activation
Mon 21:00Closed-building conditions begin (12 hours before the test starts)MAH 7.3.2
Tue 9:00Earliest the test can begin (24 hours after the fan)SGM-SF 9.2
Thu 9:00A 48-hour short-term test ends; the lab or monitor result followsPennsylvania's minimum test length
Within 10 business days of the testWritten results to the client and the owner or occupant, in pCi/L25 Pa. Code 240.303 (3)
Day 30Last day for the first test to be placed under SGM-SF 9.2 unless the 13.6.2 exception appliesBuyer's side usually wants the number well before this
Month 3If nobody has answered, a test kit goes to the occupantSGM-SF 9.2.3.1

If the result is under 4 pCi/L the job is functionally done, but the paperwork is not. EPA also says to consider fixing between 2 and 4 pCi/L, and the MAH report language says to include that advisory for low results (MAH 2019, section 8.5.9).

What the paperwork has to say about retesting

After the first test, the retest clock moves to the owner, but the contractor has to put it in front of them. SGM-SF section 10.1 requires an information package labeled "Radon Mitigation Information" or similar, attached to the system in a visible spot or otherwise given to the client. It must include:

  • A recommendation to retest at least every 2 years, and as the MAH protocol or local rules otherwise say.
  • A description of the fan monitor(s), a recommendation to check them monthly, the documented startup gauge readings, and what to do if the monitor shows degradation or failure.
  • The system as installed, as a narrative or a floor plan sketch with parts labeled.
  • Observations that might affect the system or other building systems, and any deviations from the standard or state rules.
  • The contractor's limitations on future obligations, and contact details for the responsible qualified professional.

EPA's own consumer guide gives the same advice in plainer words: most suction systems include a monitor that shows whether the system is operating, and "it's a good idea to retest your home every two years" (US EPA, A Citizen's Guide to Radon, 2005 revision, copy hosted by Kossuth County).

When to retest sooner

The MAH report advisories list the triggers beyond the calendar. Retest when:

  • a new addition is built or the building is reconfigured or rehabilitated;
  • a ground-contact area that was not previously tested is occupied, or the home is newly occupied;
  • heating or cooling systems are significantly altered;
  • ventilation changes through extensive weatherization or mechanical work;
  • there are new openings to soil, such as altered sumps, drain tile or shower and tub retrofits, or major settlement cracks;
  • an earthquake, nearby blasting or a sinkhole occurs;
  • the mitigation system itself is altered, modified or repaired.

Add the rule of thumb in the same section: retest in conjunction with any sale. Systems that are not suction based have their own clock: for passive efforts, pressurization or dilution, the advisory is to repeat post-mitigation testing within the first year to confirm the result holds in both the heating and cooling seasons (MAH 2019, section 8.5.9.3; SGM-SF section 12).

The multifamily version is heavier

Minnesota's Department of Health publishes an operation, maintenance and monitoring addendum for systems that are not maintained by the occupant, for example rental buildings. It asks the owner to test all buildings at the property at least every 5 years under ANSI/AARST MALB-MF, including all ground-contact dwellings and occupied non-residential rooms, not less than 10% of dwellings and non-residential rooms on each upper floor, and any mitigated areas on upper floors. Between those clearance tests, previously tested locations and mitigated areas are retested at 2-year intervals. The 2-year tests may be suspended only if the required effectiveness has been consistently shown for at least 8 years and the system is inspected quarterly to verify fan operation and every 2 years for mechanical performance, with a 5-year retest still due. Each testing event includes a mechanical inspection by a qualified professional (Minnesota Department of Health, OM&M Manual for Systems Not Maintained by the Occupant, updated 10/14/2025).

The same checklist is a good model for the monthly look in a house: confirm the fan is labeled, powered and its GFCI not tripped; read the manometer, and if the fluid or indicator is at zero or well away from the marked reading, call the licensed installer; confirm the active notification monitor has power; and check the pipe, sealing and any crawl space membrane.

What Pennsylvania wants recorded

For mitigation work that is reported to Pennsylvania DEP, the report includes the certified individual's name and number, the building address, the date of initial fan activation or the alteration, the type of building and installation, the cost to the client and the post-mitigation result. Laboratory and primary tester results are due within 45 days of the analysis date, the mitigation certified individual keeps the documentation for 5 years, and the client gets the results in writing within 10 business days after testing (25 Pa. Code 240.303). Other states differ; Minnesota, Illinois and New Jersey add their own tags, licenses and records.

Why this goes wrong in practice

The National Radon Proficiency Program warns that sellers often hire a mitigator after an elevated result and shop for the lowest price, focused on getting a post-mitigation report below the action level, while buyers rarely look at radon again after closing. NRPP says most of its complaints could have been prevented if a trained inspector had evaluated the installation and given the buyer a detailed report (Home Inspector / NRPP, Behind the New Radon Mitigation Compliance). The dates above are the cheap part. What costs money is a missing startup reading, a test that was not under closed-building conditions, or a retest that nobody scheduled.

How to set this up

A radon company needs one job record that carries every date and number above, and something that chases them. The fields: fan activation timestamp, startup manometer reading, closed-building start, test device ID and type, who is testing (independent, contractor or occupant), test placement location, test start and end, result in pCi/L, client notified date, state report date, the 3-month kit-forward date, and the next retest date at 2 years.

In Fieldproxy, the setup described in the radon mitigation software guide puts those on the job and a Watcher agent flags any job where the fan is on but no test is placed by day 25 of 30, or a manometer reading at close-out is missing. The Autopilot agent drafts the "your 2-year retest is due" messages for the owner to approve, and the Scheduler agent emails the office a weekly list of jobs whose retest or state report is coming due. The mobile app records the startup gauge reading and photos on site, and the PDF "Radon Mitigation Information" package is generated from your own template so the retest recommendation is always attached.

FAQ

**How soon after a radon mitigation system is installed should you test?** No sooner than 24 hours after the system is operational and within 30 days of installation, under ANSI/AARST SGM-SF section 9.2. A state may set a longer minimum test length; Pennsylvania's short-term tests run 48 hours to 90 days.

**Why 24 hours and not immediately?** The standard builds in time after the fan starts, and the MAH protocol also requires closed-building conditions for 12 hours before and during the test. If either is not met, the test has to be postponed or extended to at least 46 hours of qualifying data on a continuous monitor.

**Can the contractor test their own system?** Under SGM-SF 9.2.3 the contractor can, if they are a qualified measurement professional and local law allows it, but they must recommend that the client use an independent professional to avoid the appearance of conflict of interest. Local rules may be stricter.

**How often should you retest after mitigation?** At least every 2 years to verify the system still works, and every 5 years for the building generally, per the MAH 2019 advisories. Also retest with any sale, after renovations or additions, after heating, cooling or ventilation changes, and after any change or repair to the mitigation system.

**What if the owner never answers about the test?** SGM-SF 9.2.3.1 treats the contractor's obligation as satisfied if the client refuses access or does not respond, but if there is no response after reasonable efforts across 3 months, the contractor has to mail a test kit to the occupant.

**What should the owner check between tests?** The SGM-SF information package recommends checking the fan monitor monthly. Minnesota's checklist says a manometer fluid level at zero, or far from the marked reading, means the owner should contact the licensed installer.