Duct size calculator
Duct size follows from two numbers: how much air has to pass (CFM) and how fast you let it travel (feet per minute). Too small and the system is loud and starved; too large and you waste material and space.
Result
- Duct area needed
- 128.0 sq in (0.889 sq ft)
- Round duct, exact
- 12.8 in diameter
- Round duct, next standard size
- 14 in
- Rectangular duct at 8 in high
- 16 × 8 in (exact width 16.0 in)
How it is calculated
- Duct area (sq ft) = CFM ÷ velocity (FPM)
- Round duct diameter (in) = √(4 × area × 144 ÷ π)
- Rectangular duct width (in) = area × 144 ÷ height (in)
Worked example
800 CFM at 900 FPM needs 0.889 sq ft, or 128 sq in. That is a 12.8 in round duct, so you would fit a 14 in, or a 16 × 8 in rectangular duct.
Before you rely on it
- This is the velocity method. It does not account for friction loss over long runs or fittings; for a full design use the equal friction method and a duct calculator or Manual D.
- Typical residential design velocities: 700 to 900 FPM in supply trunks, 600 FPM in branches, 500 to 700 FPM in returns. Round up to the next standard size.
Running an HVAC business?
In Fieldproxy, duct size sums like this one sit inside your own quotes and job forms.
Questions
What size duct do I need for 400 CFM?
At 700 FPM, 400 CFM needs about 82 sq in, a 10.2 in round duct, so a 10 in is slightly tight and a 12 in is comfortable. A 12 × 8 in rectangular duct also works.
What velocity should I design ducts for?
For homes, 700 to 900 FPM in main supply trunks and about 600 FPM in branches keeps noise down. Commercial systems run higher.