Voltage drop calculator
Voltage drop is the voltage lost in the wire between the panel and the load. Long runs and small conductors lose more. Electricians check it to choose a wire size that keeps equipment running at its rated voltage.
Result
- Voltage drop
- 6.32 V
- Percent drop
- 5.27% (above the 3% recommendation)
- Voltage at the load
- 113.7 V
- Smallest size that stays within 3%
- 8 AWG
How it is calculated
- Single-phase: drop (V) = 2 × K × current (A) × one-way length (ft) ÷ circular mils
- Three-phase: drop (V) = 1.732 × K × current (A) × one-way length (ft) ÷ circular mils
- K = 12.9 for copper, 21.2 for aluminum (ohms per circular mil foot at 75 °C)
- Percent drop = drop ÷ supply voltage × 100
Worked example
A 120 V single-phase circuit carrying 16 A over 100 ft of 12 AWG copper (6,530 circular mils): 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, a 5.3% drop. Moving to 10 AWG (10,380 circular mils) brings it to 3.98 V, 3.3%.
Before you rely on it
- The NEC suggests, in informational notes, keeping voltage drop to 3% on a branch circuit and 5% across feeder and branch together. These are recommendations for efficiency, not a rule for every installation; check your local code.
- This uses the DC resistance method, which is accurate for the wire sizes listed at typical power factors. For large conductors or long AC runs, use the impedance values in NEC Chapter 9, Table 9.
Running an electrical business?
In Fieldproxy, voltage drop sums like this one sit inside your own quotes and job forms.
Questions
What is an acceptable voltage drop?
The NEC informational notes recommend no more than 3% on a branch circuit and 5% total for feeder plus branch. Sensitive equipment may need less.
How do I reduce voltage drop?
Use a larger conductor, shorten the run, lower the current on the circuit, or raise the supply voltage. Going up one wire size is the usual fix.
More calculators
See it built around how your team already works.
Get Demo