Guide for medical gas verification and maintenance companies ยท checked 28 November 2026
Medical gas verification, run outlet by outlet, zone by zone, report by report
A medical gas verifier signs off that every oxygen, medical air, nitrous oxide, nitrogen, vacuum and WAGD outlet in a hospital delivers the right gas, at the right pressure, clean, before a patient is connected to it. The same firms usually hold the annual inspection and maintenance contract afterwards. This guide covers the installer and verifier test sequence under NFPA 99, the ASSE 6000 series credentials, the pass figures in a real federal spec, zone valve and labeling rules, the annual program surveyors look for, and how to set up software around outlets, zones and reports.
See your own jobs set up this way
A 30-minute call. We show you medical gas verification and maintenance companies workflows running in Fieldproxy, built around how you work.
Short answer
Medical gas verification and maintenance companies mostly run on test forms (the ASSE 6010 installer record, their own verifier report template), spreadsheets of outlets and zone valves, and analyzer printouts, with some using a manufacturer platform such as BeaconMedaes' MyMedGas or a hospital's CMMS such as Oxmaint for the annual program. Fieldproxy is one option for the verifier's own system: a register of every source, zone valve, alarm and outlet per facility, mobile test screens that capture each NFPA 99 test with its pass figure, a verification report built from those results, and an annual inspection program with deficiencies tracked to repair.
ASSE 6030
Credential NFPA 99 requires for the verifier, who must be independent of the installer; bulk cryogenic supplies need an ASSE 6035 verifier
0.45 micron
White filter that at least 1,000 L of gas passes through at 100 L/min or more in the VA's particulate test; it may collect no more than 0.1 mg
24 hours
Installer standing pressure test at 20% above normal line pressure, and 12 inHg for vacuum; since NFPA 99-2018 a 0.5% drop is allowed
Jul 5, 2016
Date CMS started requiring the 2012 edition of NFPA 99, Health Care Facilities Code, for Medicare and Medicaid providers
How a job runs
One medical gas verification job, from first call to paid
The order the work really happens in, and what has to be written down at each step so nothing is argued about later.
- 1
Scope the job and the risk category
Get the drawings, the outlet schedule and the gases involved, and confirm whether the work is a new system, an addition or a repair tied into a live system. NFPA 99 sorts systems by risk category (Category 1 where failure is likely to cause significant injury or death). From the 2021 edition, a permit-to-work system covers work on live systems and the facility's Responsible Facility Authority accepts the verification report.
- 2
Inspect before the walls close
Since NFPA 99-2018, an ASSE 6020 inspector or ASSE 6030 verifier inspects the piping before it is concealed in walls, ceilings, chases or underground, and witnesses the installer's initial pressure tests. Check tube markings (ASTM B819 Type L or K, marked OXY, MED, OXY/MED, OXY/ACR or ACR/MED in blue or green), brazing with a continuous nitrogen purge, and labels every 20 ft.
- 3
Collect the installer's test record
The ASSE 6010 installer runs and records initial blowdown, initial pressure test (1.5 times working pressure, 150 psig minimum, nitrogen lines 240 psig), cross-connection test, piping purge test, and the 24-hour standing pressure tests, all with oil-free dry nitrogen NF. The verifier does not start until this record is complete and signed.
- 4
Run the verifier's standing pressure and cross-connection tests
The independent ASSE 6030 verifier repeats a standing pressure check, then pressurizes one system at a time with every other system at atmospheric pressure and visits each outlet to prove only the intended gas flows. This is the test that catches the crossed oxygen and nitrous oxide line before a patient does.
- 5
Test valves and alarms
Close each zone valve and confirm it isolates only the outlets on its label, with the gauge on the patient side dropping. Trip every master alarm signal and area alarm (high and low line pressure, source changeover, dew point, and for oxygen concentrator plants low concentration under 91%) and confirm the signal reaches each panel listed.
- 6
Prove the piping is clean and pure
Purge each zone at high flow, then run the particulate test at the outlet farthest from the source (in the VA spec, 1,000 L through a 0.45 micron white filter at 100 L/min or more, no discoloration, 0.1 mg maximum). Test the same outlet for dew point, carbon monoxide, total hydrocarbons and halogenated hydrocarbons, and compare against the source gas.
- 7
Make the final tie-in and test operating pressure and concentration
After tie-in to the live system, test the tie-in joints, then measure static pressure and flow at outlets (the VA spec asks 100 L/min at no more than 5 psig drop for oxygen, nitrous oxide and air, 20 SCFM for nitrogen at 210 psig static). Analyze every outlet for gas concentration with an analyzer made for that gas: medical air 19.5% to 23.5% oxygen; USP 93 oxygen 90% to 96%.
- 8
Verify source equipment and labels
Check medical air compressors (intake at least 25 ft from exhausts and vents, 20 ft above ground, 10 ft from doors and windows), dryers and the dew point and CO monitors, manifolds and changeover, vacuum pumps and their HEPA inlet filters, and the labels on sources, zone valves, outlets and pipe.
- 9
Issue the report and set up the annual program
The written verification report goes to whoever ordered the tests and, where required, the building official. The facility then needs a documented inspection, testing and maintenance program; HFM summarizes the usual annual scope as alarms, source systems, outlets and inlets, booms and flexible connectors, and the bulk oxygen system. Maintenance is done by ASSE 6040 personnel, and every repair gets the affected portion retested.
What to record
The fields every medical gas verification job should capture
Facility, systems and components
- Facility, building, Responsible Facility Authority, NFPA 99 edition the AHJ enforces (CMS: 2012), risk category per system
- Systems: oxygen, medical air, nitrous oxide, carbon dioxide, nitrogen, instrument air, medical-surgical vacuum, WAGD, each with its standard pressure
- Sources: bulk tank (supplier, NFPA 55 inspection), manifolds, compressors, dryers, vacuum pumps, concentrators, with serial and install date
- Zone valves: ID, location, gases, rooms and outlets served (as labeled), gauge on patient side, valve size and Cv
- Alarms: master panels (two locations), area alarms, local alarms, the signals each one carries
- Outlets and inlets: room, gas, connector type (DISS or quick connect, manufacturer), zone valve, boom or headwall assembly
Every verification test
- Test name (standing pressure, cross-connection, valve, alarm, purge, particulate, purity, tie-in, operational pressure, concentration, medical air purity, labeling, source)
- System and zone, outlet tested, test gas (nitrogen NF or source gas), instrument and calibration date
- Reading: pressure and hold time, filter weight and photo, dew point, CO, THC, halogenated HC in ppm, oxygen %, flow in L/min with pressure drop
- Source gas comparison reading and the variation
- Pass or fail against the spec figure, verifier name and ASSE 6030 (or 6035) number, witness name
Annual inspection and maintenance
- Outlet inspection: retention, leaks, flow, labeling, damage, per outlet
- Alarm test results per signal, zone valve exercise and label check, gauge readings
- Compressor, dryer and vacuum pump PM: hours, filter changes, dew point and CO monitor calibration
- Deficiencies: code reference, risk (immediate, possible, none), photo, proposed repair, status
- Repairs: ASSE 6040 technician, permit to work, shutdown notice, affected portion retested and by whom
Rules and standards
The rules that shape the work, with their sources
| Rule | What it means on the job |
|---|---|
| CMS: NFPA 99-2012 for Medicare and Medicaid providers | CMS's final rule of 4 May 2016 requires certain providers to meet the 2012 Life Safety Code and the 2012 Health Care Facilities Code (NFPA 99). Hospitals and nursing homes are surveyed against that edition even where the local building code is newer. source: CMS, S&C 16-22-LSC: Adoption of the 2012 Life Safety Code and 2012 Health Care Facilities Code (NFPA 99) |
| NFPA 99-2012 put maintenance of existing systems in scope | Earlier editions were mostly applied to new or altered systems. The 2012 edition, moved from occupancy-based to risk-based categories, made periodic maintenance and testing of existing medical gas and vacuum systems part of the code, and bans adapters or conversion fittings between gas-specific connectors. source: Health Facilities Management, What CMS' changes mean for medical gas system regulations |
| ASSE Series 6000 credentials | 6010 installers, 6020 inspectors, 6030 verifiers, 6035 bulk medical gas and cryogenic fluid central supply verifiers, 6040 maintenance personnel, 6060 designers, and from the 2024 edition 6070 design instructors. Series 6000-2024 aligns with NFPA 99-2024. source: IAPMO, ASSE/IAPMO/ANSI Series 6000-2024 now available (11 Mar 2025) |
| Who does what (NFPA 99-2012, 5.1.14.2.2.5) | Hospital policies built on the code use 6010 installers for installation and the installer's self-tests, an independent third-party 6030 verifier for the final verification and certificate, 6030 for verified testing in the annual program, and 6040 personnel for maintenance and repair. source: NYU Langone Health, Safety Policy 133: Medical Gas Outlets and Piping (rev. July 2025, NFPA 99-2012 excerpts) |
| Inspection before concealment (NFPA 99-2018) | System inspections are performed by an ASSE 6020 inspector or 6030 verifier before piping is concealed in walls, ceilings, chases, trenches or underground, and include witnessing the initial pressure tests. Cryogenic fluid central supply systems are verified by an ASSE 6035 verifier. source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035) |
| Responsible Facility Authority and permit to work (NFPA 99-2021) | The 2021 edition names a Responsible Facility Authority whose duties include advising on risk categories and evaluating and accepting verification reports, adds a documented permit-to-work system, and requires testing of affected portions after any work. source: Consulting-Specifying Engineer, The medical gas code updates within NFPA 99 (11 Oct 2022) |
| Installer tests and test gas | Initial blowdown, initial pressure test at 1.5 times working pressure (150 psig minimum; nitrogen at 240 psig), vacuum at 60 psi on copper, cross-connection one system at a time, piping purge, 24-hour standing pressure at 20% above line pressure, 24-hour standing vacuum at 12 inHg. Test gas is nitrogen NF. source: Hamilton County Public Health, Medical Gas System Installer Performance Testing Record (ASSE 6010 / NFPA 99) |
| Standing pressure drop allowed since 2018 | The installer's 24-hour standing pressure test may drop 0.5% under NFPA 99-2018 (2015 and earlier allowed no loss), and 1% where flexible hoses on columns and headwalls are included. source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035) |
| Piping materials and labels (NFPA 99-2012, 5.1.10 and 5.1.11) | Positive pressure piping is ASTM B819 medical gas tube Type L (Type K above 185 psi for sizes over NPS 3), cleaned for oxygen service per CGA G-4.1 and delivered capped. Pipe labels go at least every 20 ft, once in or above every room, on both sides of walls penetrated and once per story on risers. source: NYU Langone Health, Safety Policy 133: Medical Gas Outlets and Piping (rev. July 2025, NFPA 99-2012 excerpts) |
| Zone valve placement and labels | A wall separates the valve from the outlets it controls, it serves only its own floor, it sits immediately outside each critical care and anesthetizing location, valves are not in series, it has a gauge on the patient side, is never in a locked room or behind a door, and its label is visible from outside the box, not on the removable cover. source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035) |
| Medical air intake and use | Medical air intake at least 25 ft from exhausts, vents and vacuum or WAGD discharges, at least 20 ft above ground, 10 ft from doors and windows. Medical air is for human respiration only; booms, brakes and instrument cleaning use instrument or nonmedical air. source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035) |
| Annual program is the facility's to define | Surveys look for a documented procedure. HFM summarizes the required inspection and testing as generally annual for warning systems, source supply systems, station outlets and inlets, booms and flexible connectors, and the bulk oxygen system, with the bulk supplier inspecting the bulk system at least yearly under NFPA 55. ASSE 6000 recommends some daily checks, such as main line pressure within plus or minus 5%. source: Health Facilities Management, Gas flow: developing a medical gas O&M program |
| Changing frequencies needs evidence (CMS 482.41(c)(2)) | CMS lets hospitals do preventive maintenance on non-critical equipment less often than the manufacturer recommends only on a systematic, evidence-based risk assessment; critical equipment is excluded. Risk-based outlet testing programs are built on this. source: GasMedix, Medical gas system testing (CMS 482.41(c)(2) risk-based frequencies) |
| Why cross-connection testing matters | On 7 Dec 2000 four residents of a Bellbrook, Ohio nursing home died and six were injured after receiving industrial nitrogen instead of oxygen. FDA counted at least 8 deaths and 16 serious injuries from medical gas mix-ups by 2006 and noted that facilities are not required to report them. source: Federal Register 71 FR 18039 (10 Apr 2006), FDA draft guidance on medical gas containers and closures (mix-up history) |
Rules vary by state, council and contract. Checked 28 November 2026; confirm against the source for your area before relying on it.
Numbers
Pressures and pass figures a verifier works to
Standard pressures are from NFPA 99-2012 Table 5.1.11 as reproduced in NYU Langone's policy. Test pass figures are from the VA master spec 22 63 00 (05-01-23), which many federal and private specs follow; always test to the project's own spec and the edition the AHJ enforces.
| Item | Figure | Source note |
|---|---|---|
| Oxygen, medical air, nitrous oxide, CO2 line pressure | 50 to 55 psig | NFPA 99-2012 Table 5.1.11 |
| Nitrogen and instrument air line pressure | 160 to 185 psig | Label the pressure if different |
| Medical-surgical vacuum | 15 to 30 inHg | WAGD varies by system type |
| Installer initial pressure test | 1.5 x working, 150 psig min | Nitrogen lines 240 psig; vacuum 60 psi on copper |
| Standing pressure test | 24 h at 20% above line pressure | 0.5% drop allowed since NFPA 99-2018 |
| Standing vacuum test | 24 h at 12 inHg | Inlets and components assembled |
| Particulate test | 1,000 L through 0.45 micron at 100 L/min+ | No discoloration, 0.1 mg max, most remote outlet per zone |
| Purity: outlet vs source variation | Dew point 2ยฐC, CO 2 ppm, THC 1 ppm, halogenated 2 ppm | VA spec maximum allowable variation |
| Outlet flow: O2, N2O, air | 100 L/min, 5 psig max drop, 50 psig static | Nitrogen 20 SCFM at 210 psig static |
| Medical air concentration | 19.5% to 23.5% oxygen | Analyzer made for the gas |
| USP 93 oxygen (concentrator plants) | 90% to 96% oxygen | Alarm under 91% at master panel |
| Medical air dew point alarm | Above 2ยฐC (35ยฐF) at line pressure | Instrument air: above minus 30ยฐC |
source: NYU Langone Health, Safety Policy 133: Medical Gas Outlets and Piping (rev. July 2025, NFPA 99-2012 excerpts)source: Hamilton County Public Health, Medical Gas System Installer Performance Testing Record (ASSE 6010 / NFPA 99)source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035)source: VA master specification 22 63 00, Gas Systems for Laboratory and Healthcare Facilities (05-01-23), via WBDG
Where it breaks
Where spreadsheets and generic software fall over
The verifier arrives and the installer's test record is missing a standing pressure test on one system, so the day is lost and the opening slips.
Make the installer record part of the job: each system has its six installer tests with date, tester and ASSE 6010 number, and the verification visit cannot be scheduled until every one is signed.
Outlet lists live in a spreadsheet built from drawings, so outlets added in a change order are never tested and never appear on the report.
Hold outlets as records under rooms and zone valves, imported from the outlet schedule and updated from site, and block the report while any outlet in scope has no cross-connection and concentration result.
Analyzer printouts, filter photos and handwritten readings are typed into a Word report days later, with transcription errors in ppm and percentages.
Capture each reading on the mobile test screen against the spec figure for that test, with instrument ID and calibration date, so pass or fail is decided on site and the report is generated from the readings.
Zone valve labels list rooms that were renumbered in a renovation, and nobody notices until a shutdown isolates the wrong ICU.
Store the rooms each zone valve serves as data, test valve isolation outlet by outlet, and flag any outlet that drops on a valve not listed on its label.
Annual inspection deficiencies go out as a PDF, the hospital approves a few repairs by email, and next year's surveyor asks what happened to the rest.
Track each deficiency with its code reference, risk rating, quote, approval and repair retest, so the hospital can show every finding closed or risk-assessed.
A tech brazes a repair on a live system without a permit to work, and the affected portion is not retested before gas is restored.
Make repair jobs on med gas require a permit (shutdown window, zones affected, clinical sign-off) and a retest step by a credentialed person before the job can close.
Checklist
The medical gas verification operations checklist
Print it, or hand it to whoever runs the office side.
- NFPA 99 edition and AHJ confirmed per project (CMS surveys to 2012)
- Risk category set for each system
- Inspection before concealment done by ASSE 6020 or 6030, initial pressure tests witnessed
- Installer tests complete and signed by an ASSE 6010 installer, nitrogen NF used
- Verifier independent of the installer, ASSE 6030 (6035 for bulk) numbers on file
- Every outlet cross-connection tested one system at a time
- Every zone valve tested for isolation and labeled with the rooms it serves
- Every master and area alarm signal tripped and confirmed at each panel
- Particulate and purity tested at the most remote outlet of each zone
- Every outlet analyzed for concentration with a gas-specific analyzer, calibration recorded
- Medical air source purity and dew point and CO monitors checked
- Verification report delivered to the client and AHJ, accepted by the RFA
- Annual program written with intervals, deficiencies tracked to repair
- Every repair on a live system under permit to work and retested
Software options
What software medical gas verification and maintenance companies actually use
Judge each one on whether it fits the way your jobs run, not on the feature list. Bring a real job to every demo.
MyMedGas (BeaconMedaes)
Hospitals and labs with BeaconMedaes equipment or inspection contracts that want the manufacturer's record of their pipeline system.
Cloud platform for compliance tracking, asset and location mapping (upstream and downstream), maintenance history, field service reports and a document library, tied to BeaconMedaes' annual inspection service.
Oxmaint
Hospital facility teams that keep the med gas PM program in their own CMMS.
CMMS with zone valves as individual assets, PM schedules for alarm panels and source equipment, and log exports by asset or building. A facilities tool, not a verifier's test and report system.
MangoApps inspection templates
Teams that want a digital checklist for one verification walk.
Template for pressure, cross-connection, particulate and final tie-in checks with the ASSE 6030 verifier's sign-off, inside a general frontline operations platform.
Paper and PDF test forms plus spreadsheets
Most small verification firms today.
ASSE 6010 installer records like Hamilton County's form, the firm's own verifier report template and an outlet spreadsheet. Cheap and familiar; outlets, readings and deficiencies are retyped and hard to trend year to year.
Fieldproxy
Verification, inspection and med gas maintenance contractors that want facilities, outlets, test readings, reports and annual programs in one system set up around their own report format.
Set up for you around your test sequence and spec figures; analyzer exports and drawings come in by file import or the open API.
Published prices, compared:source: BeaconMedaes, MyMedGas medical gas distribution management platformsource: BeaconMedaes, Annual Inspections (ASSE 6020 inspectors, deficiency dashboard)source: Oxmaint, Hospital medical gas system software (NFPA 99, EC.02.05.09)source: MangoApps, Medical Gas Piping Verification Inspection (NFPA 99) templatesource: Hamilton County Public Health, Medical Gas System Installer Performance Testing Record (ASSE 6010 / NFPA 99)
Questions to ask any vendor
- Can it hold every outlet, zone valve, alarm and source for a hospital, and which zone valve feeds which outlet?
- Does each test screen know the pass figure for that test (pressure hold, filter weight, ppm limits, flow and drop) and decide pass or fail on site?
- Can it block the verification visit until the installer's six tests are recorded and signed?
- Does it record the instrument and calibration date behind every analyzer reading?
- Can annual deficiencies be quoted, approved by the hospital and closed with a retest, and shown to a surveyor?
- Can it store each technician's ASSE 6010, 6020, 6030, 6035 or 6040 card with expiry and stop an uncredentialed tech being assigned?
Bring one real medical gas verification job. We show it running in Fieldproxy.
Get DemoHow Fieldproxy is set up for this
Medical gas verification on Fieldproxy: built around how you already work
A Fieldproxy setup for a medical gas verification company is built around the facility's outlets, zones and sources: every test is captured against the outlet or zone it belongs to with its pass figure, the verification report is generated from those readings, and the annual program keeps the same register so next year's inspection, deficiencies and repairs build on this year's.
Module 1
Facility, system and outlet register
Verification and annual testing are done outlet by outlet and zone by zone, so those are the records, not the customer.
- Record: Facility (hospital, ASC, nursing home, dental, lab; AHJ; NFPA 99 edition enforced; Responsible Facility Authority)
- Child records: System (gas, standard pressure, risk category), Source (bulk, manifold, compressor, dryer, vacuum pump, concentrator), Alarm panel (master or area, signals carried)
- Zone valve record: ID, location, gases, size and Cv, rooms served as labeled; Outlet record: room, gas, connector type and make, zone valve, assembly (boom, headwall)
- Import from the outlet schedule or a prior report; outlets added on site get a status of 'added in field' for the change order
Module 2
Verification projects and the installer gate
A verification visit wasted on an incomplete installer record costs a day and the opening date.
- Project record: contractor, GC, scope (new, addition, renovation tie-in), systems and zones in scope, target opening date
- Installer test record per system: blowdown, initial pressure, cross-connection, purge, standing pressure, standing vacuum; date, tester, ASSE 6010 number, uploaded form
- Rule: verification visit cannot be scheduled until every installer test for systems in scope is complete and signed
- Pre-concealment inspection visits with witnessed pressure tests and photos per wall or ceiling area
Module 3
Mobile verifier test screens
Readings decided pass or fail on site, against the spec, are the report.
- One screen per test: standing pressure, cross-connection, valve, alarm, purge, particulate, purity, tie-in, operational pressure, concentration, medical air purity, labeling, source
- Spec figures held per project (e.g. VA 22 63 00: 0.45 micron, 1,000 L at 100 L/min, 0.1 mg; variation dew point 2ยฐC, CO 2 ppm, THC 1 ppm, halogenated 2 ppm)
- Readings with units, source gas comparison, instrument ID and calibration date, filter photo; offline in mechanical rooms and basements
- Outlet walk ordered by zone; any outlet that delivers the wrong gas opens a Critical deficiency and stops the zone
Module 4
Verification report and certificate
The report goes to the owner, the RFA and often the building official, and must match what was tested.
- Generated from test records in the firm's own template: systems, zones, outlet tables, readings, instruments, verifier name and ASSE 6030 or 6035 number
- Block: report cannot be issued while any in-scope outlet, valve or alarm has no result or a failed result without retest
- Status: Draft, Issued, Accepted by RFA; acceptance captured by e-signature
- Report and certificate stored against the facility for next year's annual program
Module 5
Annual inspection and maintenance program
After the opening, the same outlets come back every year, plus daily, monthly and quarterly source checks if the firm holds the maintenance contract.
- Program per facility: annual outlet and alarm testing, zone valve exercise, source equipment PM (compressor hours, dryer, dew point and CO monitor calibration, vacuum HEPA filters)
- Intervals set per facility policy, with a risk-based option (e.g. high-use areas yearly, others split across quarters) recorded with its assessment
- Next due from last completed, not last scheduled; bulk oxygen supplier inspection date tracked
- Year-on-year outlet history: each outlet's results across inspections
Module 6
Deficiencies, quotes and repairs
Surveyors ask what happened to last year's findings.
- Deficiency record: outlet, valve or source; code reference; risk (immediate threat, possible threat, none); photo
- Quote from the deficiency, hospital approval, scheduled repair
- Repair job requires a permit to work (shutdown window, zones affected, clinical sign-off) and closes only with the affected portion retested
- Open deficiency list per facility on demand for the RFA
Module 7
Credentials and dispatch
Who may install, inspect, verify or maintain is set by the ASSE 6000 credential, and the verifier must be independent.
- Technician cards: ASSE 6010, 6020, 6030, 6035, 6040, CMGV, state endorsements (e.g. Texas Medical Gas Piping Installation), expiry dates
- Rule: a verification job cannot be assigned to anyone who worked on that project's installation
- Rule: bulk cryogenic supply verification only to ASSE 6035 holders
- Instrument register: analyzers, particulate kit, flow meters, calibration due dates; a test cannot use an out-of-calibration instrument
Module 8
Hospital portal
The RFA, facilities director and accreditation team need the reports, deficiencies and credentials without emailing the contractor.
- Per facility: current verification reports, annual inspection reports, open deficiencies with status, technician credentials for each visit
- Approve quotes and repair windows from the portal
- Survey pack export: program, last inspection, deficiencies closed, credentials
The AI agents, set up for medical gas verification and maintenance companies
| Agent | When | What it does | What you get |
|---|---|---|---|
| Document intelligence agent | A GC emails the outlet schedule, plumbing drawings legend or a prior verifier's PDF report. | Reads rooms, gases, outlet counts and zone valve IDs, and the previous report's outlet tables and readings. | Draft outlet and zone valve records under the facility, flagged where the count differs from the drawings. |
| Vision agent | The verifier photographs a zone valve box label, an outlet face or an analyzer screen. | Reads the gases and rooms on the label, the outlet make and connector type, and the analyzer's percentage or ppm value. | The zone valve's rooms-served field and the test reading filled in, with the photo attached to the record. |
| Watcher agent | A verification report is in draft, or a facility's annual inspection or a technician's ASSE card is coming due. | Checks for in-scope outlets with no result, failed tests without retest, instruments past calibration, and annual dates within 60 days (e.g.). | A list on the project or facility of what blocks the report or the next visit, sent to the project lead. |
| Autopilot | Annual inspection deficiencies have a quote sent and no hospital approval after 14 days (e.g.). | Drafts a short follow-up to the facilities director listing open immediate and possible-threat items with their quotes. | A chase email a person approves before it sends, logged on each deficiency. |
| Scheduler agent | Every Monday morning. | Gathers verification visits this week, projects waiting on installer records, annual inspections due next month, and open deficiencies by facility. | A weekly briefing emailed to operations and each account manager. |
Straight answers
Medical gas verification: FAQ
What software do medical gas verification companies use?
Most use paper or PDF test forms, a Word report template and spreadsheets of outlets, plus analyzer printouts. Some hospitals keep the annual program in a CMMS such as Oxmaint or in a manufacturer platform such as BeaconMedaes' MyMedGas. Fieldproxy is one option for the verifier's own system: outlets, zones and sources as records, mobile test screens with the spec's pass figures, and reports and annual programs built from the readings.
Who is allowed to verify a medical gas system?
An ASSE 6030 medical gas systems verifier who is independent of the installer. Bulk medical gas and cryogenic fluid central supply systems are verified by an ASSE 6035 verifier. Installers hold ASSE 6010, inspectors ASSE 6020 and maintenance personnel ASSE 6040.
What is the difference between installer tests and verifier tests?
The installer runs initial blowdown, initial pressure, cross-connection, piping purge and 24-hour standing pressure and vacuum tests with nitrogen NF. The independent verifier then repeats standing pressure and cross-connection and adds valve, alarm, purge, particulate, purity, final tie-in, operational pressure, gas concentration, medical air purity, labeling and source equipment tests.
How is the particulate test done?
In the VA's master spec, at least 1,000 liters of gas flows through a clean white 0.45 micron filter at 100 L/min or more at the outlet farthest from the source in each zone. The filter must show no discoloration and collect no more than 0.1 mg. Use the figures in your project's own spec.
Which edition of NFPA 99 applies?
CMS requires the 2012 edition for Medicare and Medicaid providers, effective 5 July 2016. New construction is often designed to a newer edition (2018, 2021 or 2024) adopted by the state or named in the spec. Confirm the edition with the AHJ before testing.
How often do medical gas systems need testing after they are verified?
The facility sets intervals in a documented program. The usual scope is annual testing of alarms, source systems, outlets and inlets, booms and flexible connectors, with the bulk oxygen system inspected by the supplier at least yearly, and some checks such as main line pressure done daily. Hospitals may test non-critical items less often than the manufacturer recommends only on an evidence-based risk assessment.
Is a standing pressure test allowed to lose pressure?
Under NFPA 99-2018 the installer's 24-hour standing pressure test may drop 0.5%, and 1% where flexible hoses in columns and headwalls are included. The 2015 and earlier editions allowed no loss.
What must be retested after a repair?
Under NFPA 99-2021 the affected portion of the system is tested after any work, under a documented permit-to-work system, and the Responsible Facility Authority evaluates and accepts the verification report.
Do medical gas installers need a state license?
It depends on the state. Texas, for example, issues a Medical Gas Piping Installation endorsement to licensed plumbers, renewed with continuing education. Many hospitals and specs also require ASSE 6010 regardless of state rules.
Can Fieldproxy produce our verification report format?
Yes. The report is generated from your own template, filled from the test readings, outlet tables and credentials captured on site. Analyzer exports and prior reports can be imported.
Related guides
All sources on this page (27)
- source: NY State OGS master spec 22 60 00, Gas and Vacuum Systems for Laboratory and Healthcare Facilities
- source: VA master specification 22 63 00, Gas Systems for Laboratory and Healthcare Facilities (05-01-23), via WBDG
- source: Hamilton County Public Health, Medical Gas System Installer Performance Testing Record (ASSE 6010 / NFPA 99)
- source: CMS, S&C 16-22-LSC: Adoption of the 2012 Life Safety Code and 2012 Health Care Facilities Code (NFPA 99)
- source: Health Facilities Management, What CMS' changes mean for medical gas system regulations
- source: IAPMO, ASSE/IAPMO/ANSI Series 6000-2024 now available (11 Mar 2025)
- source: NYU Langone Health, Safety Policy 133: Medical Gas Outlets and Piping (rev. July 2025, NFPA 99-2012 excerpts)
- source: ASPE Rochester / Evergreen Medical Services, NFPA 99 2018 applicable med gas changes (Russ Kopylczak, ASSE 6030/6020/6010/6035)
- source: Consulting-Specifying Engineer, The medical gas code updates within NFPA 99 (11 Oct 2022)
- source: Health Facilities Management, Gas flow: developing a medical gas O&M program
- source: GasMedix, Medical gas system testing (CMS 482.41(c)(2) risk-based frequencies)
- source: Federal Register 71 FR 18039 (10 Apr 2006), FDA draft guidance on medical gas containers and closures (mix-up history)
- source: BeaconMedaes, MyMedGas medical gas distribution management platform
- source: BeaconMedaes, Annual Inspections (ASSE 6020 inspectors, deficiency dashboard)
- source: Oxmaint, Hospital medical gas system software (NFPA 99, EC.02.05.09)
- source: MangoApps, Medical Gas Piping Verification Inspection (NFPA 99) template
Run medical gas verification and maintenance work the way it actually runs.
A 30-minute call. We set up one of your real jobs in Fieldproxy so you can judge it on your own work.
Get a walkthroughOne price per company. Unlimited users.